Technical Specifications
DGA Method: Laboratory Grade Gas Chromatography |
| Accuracy¹ | Repeatability² | Range³ |
| Hydrogen (H2 ) | ±5% or ±3 ppm | <2% | 3-3,000 ppm |
| Oxygen (O2) | ±5% or +30/-0 ppm | <1% | 30-25,000 ppm |
| Methane (CH4 ) | ±5% or ±5 ppm | <1% | 5-7,000 ppm |
| Carbon Monoxide (CO) | ±5% or ±5 ppm | <2% | 5-10,000 ppm |
| Carbon Dioxide (CO2 ) | ±5% or ±5 ppm | <1% | 5-30,000 ppm |
| Ethylene (C2 H4 ) | ±5% or ±3 ppm | <1% | 3-5,000 ppm |
| Ethane (C2 H6 ) | ±5% or ±5 ppm | <1% | 5-5,000 ppm |
| Acetylene (C2 H2 ) | ±5% or ±1 ppm | <2% | 1-3,000 ppm |
| Nitrogen (N2 ) | ±10% or ±5,000 ppm | <20% | 5,000-100,000 ppm |
|
| All specifications are independent of oil temperature and gas pressure levels | ||
|
| 1) Percent or PPM - whichever is greater | ||
|
| 2) At the calibration leve | ||
|
| 3) Gas-in-Oil | ||
Additional Monitoring Options |
| Accuracy4 | Range | |
| Moisture-in-Oil |
| ±2% | 0-100% RS |
|
| < 10% of reading for oil temperature | > 30°C | 0 to 805 ppm |
|
| < 18% of reading for oil temperature | < 30°C | 0 to 805 ppm |
| Oil Temperature |
| 0.1°C (typically) | -40°C to +180°C |
|
| 4) Includes non-linearity and repeatability | ||
|
| 5) Upper range limited to saturation | ||
Total Dissolved Gases | True Total Combustible Gas | True Total Dissolved Combustible Gas (TDCG) output is available reporting 100% of detected level in PPM for H2 , C2 H2 , C2 H4 , CO, CH4 , C2 H6 | ||
| Total Hydrocarbons | Total Hydrocarbons (THC) output is available reporting 100% of detected level in PPM for CH4 , C2 H2 , C2 H4 , C2 H6 | ||
Gas Analysis Parameters | Gas Analysis Parameters | Oil sampling is continuous and gas analysis intervals are user-selectable from 2 hours to 12 hours (Default: 4 hours). Automatic schedule acceleration when rate of change alarm limit is exceeded (Default: 1 hr) | ||
| Data Management | All data is date and time stamped and up to two years of data is stored in memory | ||
| Automated Calibration Verification | System performs periodic automated calibration verification to National Institute of Standards and Technology (NIST) traceable gas standard | ||
Alarms | Two individually programmable relays | 50 VDC or 240 VAC @ 3 A max. (125 VDC @ 1 A max.); relay contacts operate as normally open or normally closed | ||
| Supported Alarms | Gas Caution & Alarm for Level (ppm), Rate-of-Change (ppm/day), Power and/or Service Event | ||
External Sensor Inputs | Analog Inputs | Three (3) analog 4 to 20 mA inputs, ambient temperature sensor included. Optional sensors include transformer load guide and moisture[1]in-oil with temperature probe (uses 2 inputs) | ||
Communications | Standard Interfaces | RS-232, RS-485, Ethernet Fiber (100Base-FX), V.92 Internal POTS modem | ||
| Optional Interfaces | Cellular modem, Ethernet Copper (10/100Base-TX), Wireless Radio | ||
| Supported Protocols | TCP/IP, DNP3, Modbus RTU, ASCII, OPC and IEC 61850 | ||
Environmental Specifications | Operating Temperature | -50°C to +55°C |
|
|
| Cold Start Temperature | -20°C |
|
|
| Operating Humidity | 5% to 95% RH, non-condensing |
|
|
| Oil Inlet Pressure | 0 to 45 psi (0 to 3 bar) |
|
|
| Storage Temperature | -40°C to +75°C |
|
|
| Storage Humidity | 5% to 95% RH, non-condensing |
|
|
Physical Specifications | Product Dimensions | HxWxD: 22.0 in x 20 in x 11.2 in (55.9 cm x 50.8 cm x 28.4 cm) | ||
| Packaging Dimensions | 26.4 in x 26.4 in x 15.9 in (67 cm x 67 cm x 40.3 cm) | ||
| Product Weight | 65 lb (29.5 kg) | ||
| Shipping Weight | 70 lb (31.8 kg) (monitor package only) | ||
| Enclosure Rating | NEMA 4X, IP66 | ||
Input Power Requirements | Voltage | 115 VAC or 230 VAC ±15% | ||
| Frequency | 50/60 Hz | ||
| Current | 6 A maximum @ 115 V; 3 A maximum @ 230 V | ||
Radiated and Conducted Emissions |
| Specification | Test Method |
|
| Radiated Emissions | EN 61326-1: 2006 | CISPR 11: 2009 A1: 2010 Class A |
|
| Conducted Emissions | EN 61326-1: 2006 | CISPR 11: 2009 A1: 2010 Class A |
|
| Current Harmonics | EN 61000-3-2: 2006 | EN 61000-3-2: 2006 A1: 2009 Class A |
|
| Voltage Fluctuations | EN 61000-3-3: 2008 | EN 61000-3-3: 2008 Class A |
|
Radiated and Conducted Immunity |
| Specification | Test Method |
|
| ESD | EN 61326-1: 2006 | IEC61000-4-2: 2009 |
|
| Radiated Immunity | EN 61326-1: 2006 | IEC61000-4-3: 2006 A2: 2010 |
|
| EFT | EN 61326-1: 2006 | IEC61000-4-4: 2004 A1: 2010 |
|
| Surge | EN 61326-1: 2006 | IEC61000-4-5: 2006 |
|
| Conducted RF Immunity | EN 61326-1: 2006 | IEC61000-4-6: 2009 |
|
| Magnetic Field Immunity | EN 61326-1: 2006 | IEC61000-4-8: 2010 |
|
| Voltage Dips & Interrupts | EN 61326-1: 2006 | IEC61000-4-11: 2004 |
|
Safety |
| Specification |
|
|
|
| IEC 61010-1 |
|
|
|
| IEC 61010-2-81 |
|
|
|
| UL 61010-1 (2nd Edition) |
|
|
|
| CSA-C22.2 No. 61010-1-04 |
|
|