Technical Specifications
Power supply | Voltage range | 88 - 300 VDC / VAC, 42.5 to 67.5 Hz (optional 36 - 72 VDC) |
| Power | 20 VA |
| Auxiliary output | DC output 12 VDC at 750 mA |
MMI | Display | Backlit LCD, 114 x 49mm - 240 x 80 dots |
| Keypad | 7 button membrane keypad |
| Status | 9 LEDs (healthy, alarm, trigger, clock sync, comms, status) |
Line modules | TWS FL-1 | Fixed format with one line module |
| TWS FL-8 | 2 line modules expandable to 8 in steps of 2 |
| Channels | 3 (one per phase) from external linear couplers - 12 bit ADC |
| Gain | Programmable full scale deflection |
| Triggering | Programmable threshold level |
| Sample rate | 20 MHz, 10 MHz, 5 MHz, 2.5 MHz or 1.25 MHz |
| Diagnostics | Automatic test of channel front end to prove operation |
Digital inputs | 2 per line module | Wide ranging input from 48 to 250 VDC - selectable debounce |
Storage | CompactFlash | 4 GB allowing storage of 2100 records from 8 line modules at a sampling rate of 2.5 MHz (option for 8GB on request) |
| Modes | Selectable locked or cyclic buffer |
Clock | Internal | Synchronized by internal GPS module (master) or via NTP over LAN and a 1 pps (slave |
| Accuracy | Master 100 ns. Slave 1 microsecond |
| Output | IRIG-B out to synchronize other IEDs |
GPS antenna | Lead length | 10 meters [33 feet] (optional extension leads available) |
| Mounting | Via 25mm [1 inch] pipe mast |
Comms | Modem (optional) | Internal PSTN (V.90) modem (optional on COM 4) |
| Ethernet port | 2 x 100 Mbits - one RJ45 for local connection at the front and one RJ45 (with option for fiber) on the rear port |
| USB | One port to facilitate firmware upgrade and manual download of data |
| Serial | 3 x RS 232 provided (one front panel, two on rear). 1 x RS 485 on rear panel |
Alarms | 4 provided | 1 (normally closed) for system healthy 3 (normally open) for lost lock, trigger and high priority trigger and fixed buffer 80% full |
Configuration | iQ+ Master station | Edit configuration and view diagnostics |
| Web page | Access via browser - edit settings, manual trigger, view last waveform |
Environmental | Temperature | Operating: -5 to +50º C [23 to 122º F]. Storage: -30 to +70º C [-22 to 158º F] |
| Humidity | 0 to 95% non-condensing |
Immunity | IEEE, EU and IEC | Conforms to relevant specifications for monitoring / control equipment in HV substations |
Mechanical | Enclosure | IP 41, 19” rack-mountable |
| TWS FL-8 | 3U device - H x W x D: 132.5 mm [5.2”] 487 mm [19.2”] x 362.2 mm [14.3”] Weight - 11 kg [24.2 lbs]. |
| TWS FL-1 | 2U device - H x W x D: 90 mm [3.25”] x 487 mm [19.2”] x 362.2 mm [14.3”] |